Critical Clearing Time (CCT) analysis

Intermediate

Prerequisites: Single deterministic simulation

What is CCT?

CCT (Critical Clearing Time) is a classic transient-stability metric:

"After a fault, how many seconds can pass before clearing it, and still keep the system stable?"

  • Cleared early → short disturbance, system recovers.
  • Cleared late → rotor angles drift too far apart, the system loses synchronism.

CCT is the boundary between stable and unstable. Algorithmically it's a bisection search: try fault durations in [low, high] repeatedly, narrowing in on the boundary.

YAML template

mode: cct

case_pf:  case39
case_dyn: case39dyn
power_flow: {kind: newton}
solver:     {kind: modified_euler}

cct:
  bus: 16             # faulted bus
  t_fault: 0.2        # fault apply time (fixed)
  low: 0.01           # bisection lower bound (must be stable)
  high: 0.30          # bisection upper bound (must be unstable)
  tol: 0.005          # convergence tolerance [s]
  max_iter: 15        # maximum bisection iterations
  stability_filter:
    kind: angle_stability      # how to judge stability
    params:
      max_dev_deg: 180.0

verbose: 1

Run it

python -m pylectra run examples/cct_case39.yaml

Output:

[cct] bracket check: low=0.01, high=0.3 (snapped to step 0.001)
[cct] iter  0: duration=0.1500 → unstable
[cct] iter  1: duration=0.0750 → stable
[cct] iter  2: duration=0.1125 → stable
[cct] iter  3: duration=0.1310 → unstable
[cct] iter  4: duration=0.1218 → stable
[cct] iter  5: duration=0.1264 → stable
[cct] iter  6: duration=0.1287 → unstable
[cct] iter  7: duration=0.1276 → unstable
[cct] CCT ≈ 0.1264 s (bracket [0.1264, 0.1276], 8 iters, converged=True)

Each iteration runs a full simulation (~10 total). For case39 + bus 16, CCT ≈ 127 ms.

Bracket sanity checks

Before bisecting, pylectra verifies:

  • duration = low → must be stable (otherwise CCT lies below low; result invalid).
  • duration = high → must be unstable (otherwise CCT lies above high; bracket misses it).

If either check fails, no bisection runs — instead a warning:

CCT outside bracket [0.01, 0.30]; widen the bracket.

Choosing a stability criterion

cct.stability_filter defines "what counts as stable". Two common picks:

stability_filter:
  kind: angle_stability
  params:
    max_dev_deg: 180.0    # any rotor angle further than 180° from the COI = lost synchronism

180° is the textbook first-swing threshold. For conservative studies use 120° or 90°.

voltage_range (voltage stability)

stability_filter:
  kind: voltage_range
  params:
    vmin: 0.7
    vmax: 1.2
    tail_fraction: 0.3

Counts as "voltage-unstable" if bus voltages don't recover to the band after the fault.

Composite criteria

Only one stability_filter allowed. To enforce "angle-stable AND voltage-stable", write a custom filter (how-to) that ANDs multiple criteria.

Programmatic call

from pylectra.run import run

out = run("examples/cct_case39.yaml", verbose=0)
print(f"CCT = {out.result.cct * 1000:.1f} ms")
print(f"  bracket:   [{out.result.bracket_low:.4f}, {out.result.bracket_high:.4f}]")
print(f"  iters:     {out.result.iterations}")
print(f"  converged: {out.result.converged}")

Use case: CCT-by-bus sweep

from pylectra.run import run
import matplotlib.pyplot as plt

buses = [4, 14, 16, 21, 23, 26, 29]
ccts = []
for b in buses:
    out = run("examples/cct_case39.yaml",
              cct={"bus": b, "t_fault": 0.2, "low": 0.01, "high": 0.40,
                   "tol": 0.005, "max_iter": 15,
                   "stability_filter": {"kind": "angle_stability",
                                        "params": {"max_dev_deg": 180.0}}},
              verbose=0)
    ccts.append(out.result.cct)
    print(f"bus {b}: CCT = {out.result.cct*1000:.1f} ms")

plt.bar([str(b) for b in buses], [c * 1000 for c in ccts])
plt.xlabel("faulted bus")
plt.ylabel("CCT [ms]")
plt.show()

Slow (~10 sims per bar × 7 = 70 sims). Speed up with scipy_dop853 or wrap the loop in joblib.

FAQ

Q: Why pick a [0.01, 0.30] bracket?

Too narrow triggers the bracket-sanity failure; too wide wastes iterations. Rule of thumb:

  • IEEE benchmark cases (39 / 68 / 118): [0.01, 0.40].
  • Small microgrids: [0.001, 0.10].
  • Large transmission grids: [0.05, 0.50].

Q: What does tol: 0.005 mean?

The bisection stops once bracket_high - bracket_low ≤ 0.005 s. 5 ms precision is usually enough — CCT itself has ±10 ms physical uncertainty driven by fault type and protection coordination.

Q: Power flow + initialisation re-runs every iteration?

Yes — fault duration changes the event schedule. The case itself doesn't change so PF always converges (one less thing to debug).

Q: Does the modified_euler solver introduce step quantisation?

Yes. With a 1 ms step, events can only fire on integer milliseconds. pylectra's CCT runner snaps candidates to the step grid automatically, so tol < stepsize is meaningless. Adaptive solvers (scipy_dop853) avoid this.

Using CCT as a batch filter

CCT itself is a top-level mode, but you can also use it the other way around — only accept scenarios in batch mode whose CCT exceeds a threshold. That's an advanced pattern: write a custom filter that internally runs a CCT sub-procedure. See the custom-filter how-to.